<7. Setting Parameters>

7-19

IM 01C50E01-01EN

Table 7.4

Diagnostic Results Summary

Diagnostic Status

Contents

Alert Type

NAMUR

NE107

Categor

Diagnostic Status Detail

Description

Faults in electronics

127

F

AMP ERR

Amplifier failure

MEMORY ERR

Memory failure

FlashROM ERR

FlashROM failure

ADC ERR

ADC failure

Faults in sensor or actuator

element

126

F

SENSOR1 FAILURE

Sensor 1 burnout

SENSOR2 FAILURE **

Sensor 2 burnout

TERM SNS FAILURE

CJC sensor burnout

Installation, calibration

problem

125

C

SENSOR1 SPAN ADJ ERR

Sensor 1 faulty input of span

adjustment value

SENSOR1 ZERO ADJ ERR

Sensor 1 faulty input of zero

adjustment value

SENSOR2 SPAN ADJ ERR ** Sensor 2 faulty input of span

adjustment value

SENSOR2 ZERO ADJ ERR ** Sensor 2 faulty input of zero

adjustment value

Out of service

124

C

AI1 O/S MODE

AI1 O/S Mode

AI2 O/S MODE **

AI2 O/S Mode

Outside sensor limits

123

O

---

---

Environmental conditions

out of device specification

122

O

SENSOR1 TEMP HI

Sensor 1 temperature higher

limit scale out

SENSOR1 TEMP LO

Sensor 1 temperature lower

limit scale out

SENSOR2 TEMP HI **

Sensor 2 temperature higher

limit scale out

SENSOR2 TEMP LO **

Sensor 2 temperature lower

limit scale out

AMB TEMP HI

Ambient temperature higher

limit scale out

AMB TEMP LO

Ambient temperature lower

limit scale out

Fault prediction:

Maintenance required

121

M

FIRMWARE CONDITION

CHECK

Firmware internal error

Power is critical low:

maintenance need short-

term

120

M

CRITICAL LOWBAT **

Deep sleep due to low battery

LOWBAT FOR DEEPSLEEP * Deep sleep due to low battery

Power is low: maintenance

need mid-term

119

M

LOWBAT

Low battery

Software update incomplete

118

C

---

---

Simulation is active

117

C

AI1 SIMULATE MODE

AI1 SIMULATE Mode

AI2 SIMULATE MODE **

AI2 SIMULATE Mode

* :

Applicable for single input type with integral antenna, Amplifier housing code 7.

** : Applicable for dual input type with detachable antenna, Amplifier housing code 8 and 9.

7.4.3 Checking with Integral Indicator

NOTE

If an error is detected by running self-diagnostics,

an error number is displayed on the integral

indicator. If there is more than one error, the error

number changes at three-second intervals. See

table 8.4 regarding the alarm codes.

F0706.ai

Self-diagnosis Error

(Transmitter error)

Figure 7.4

Error Check with Integral Indicator