Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 65

Advertising
background image

<9. Parameter Summary>

9-4

IM 01C50E01-01EN

Object

ID

Attribute

ID

Label

Description

Default value Handling

4.

TRANSDUCER

block

1

Tag Description

Memo field available to write anything.

Transducer

W

2

Model

Indicates the model name of the transmitter.

---

R

3

Serial Number

Indicates the device number of the transmitter.

---

R

4

Burn Out

*3

Hardware Burn

Out Switch

*2

Indicates the direction of the burnout switch on the integral

indicator. (Burnout Low / Burnout High)

Burn out High R

5

Wireless Status

Indicates the wireless communication status

1. Indicates either the initial Idle status or Join status.

(Idle status / Join status)

2. Indicates whether Contract (Pub) has been established.

(Not established / Established)

3. Indicates whether Contract (R/W) has been established.

(Not established / Established)

1. Idle status

2. Not

established

3. Not

established

R

6

Display Selection Selects the LCD display

1. Indicates the display status of the AI1/AI2 PV value.

(Displayed / Not displayed)

Displayed

W

7

LCD Mode

Selects the LCD mode.

1. Indicates the On/Off mode. (Off / Intermittent)

2. Indicates whether or not Continue.

( Continuous Off / Continuous On)

3. Indicates the bar graph display

(Bar graph: Not displayed / Bar graph: Displayed.)

1. Off

2. Continuous

Off

3. bar graph

displayed

W

8

YTA Option

Indicates the optional function supported by the device. This

cannot be changed by the user..

1. Indicates the unit system used. (SI system / Other)

Specify when

ordering

R

9

Special Cmd

Special function parameter.

0. Initial value at the time of reading (None)

1. Squawk mode

2. Deep-sleep mode

To start from the deep-sleep mode, either remove and reinsert

the battery pack or use the provisioning device tool or the device

configuration tool via infrared communication.

0

W

11

Power Saving

Mode

*2

Selects the power saving mode

0.Off (Disable)

1.On (Enable)

1

W

12

Mesurement Rate

*2

Indicates the measurement period of process values.

30 seconds

R

14

LCD Intermittetnt

Time

*2

Set the time to turn off display on the LCD indicator.

Unit: second

60 seconds

W

5.

AI1 block

6.

AI2 block

*2

1

Process Value

AI1/AI2 is a temperature output object.

Indicates the primary analog value (or corresponding process

value) and status used to execute this function.

Allows updating data by specifying this for the Concentrator

object.

1. Value: AI1/AI2 output value.

2. Status: Indicates the status of the AI1/AI2 output value.

1. ---

2. ---

W

2

Mode

A universal parameter to indicate the block’s operation status.

O/S, Auto, and Man can be selected.

1. Target: Specifies the AI1/AI2 mode.

2. Actual: Indicates the present AI1/AI2 mode.

3. Permitted: Indicates the mode that can be specified in

Target.

4. Normal: Indicates the AI1/AI2 normal status mode.

1. Target =

Auto

2. Actual =

Auto

3. Permitted

= Auto |

Manual |

OOS

4. Normal =

Auto

W

3

Concentrator OID Indicates the Concentrator object value that corresponds to the

data update of the PV value.

---

R

Advertising