Cb sets the data output format, Fc transmits screen image data, Fe transmits setup data – Yokogawa Button Operated MV2000 User Manual

Page 113: Fd transmits most recent measured/computed data

Advertising
background image

4-40

M-4662

CB

Sets the data output format

Syntax

CB p1<terminator>
p1

Output format

0

Standard output (including the
data of SKIP and OFF channels)

1

Do not output the data of SKIP and
OFF channels

Description • This setting is independent for each

connection.

• This command only affects the communication

section and has no effect on the front panel
settings.

• Valid range of commands

Output data

Corresponding
command

Instantaneous data (binary)

FD1, FF

Instantaneous data (ASCII)

FD0

Decimal place and unit information
(ASCII)

FE1

Setup channel information (binary)

FE5

Configured alarm output (binary)

FE6

Note

Initialization of BO/CS/IF/CB command settings
• For serial communications
Settings entered using the BO/CS/IF/CB commands revert

to their default values when the MV is reset (when the MV is
power cycled or the user exits from Basic Setting Mode).

• Byte output order, checksum, data output format: 0
• Status filter: 255.255.255.255
If you reset the MV, specify these settings again.
• For Ethernet communications
Settings entered using the BO/IF/CB commands revert to their

default values when the connection to the MV is dropped. After
reconnecting the MV, specify the settings again.

4.8 Output Commands

(Setting/Measured/
Computed Data Output)

FC

Transmits screen image data

Syntax

FC p1<terminator>
p1

GET (Output the screen image data)

Example

Output screen image data from the MV.
FCGET

Description Captures the current MV screen and transmits

the data in PNG format.

FE

Transmits setup data

Syntax

FE p1,p2,p3<terminator>
p1

Output data type

0

Setting commands setup data

1

Decimal place and unit information

2

Basic setting commands setup
data

4

Setup data file

5

Setup channel information output

6

Alarm information output

p2

First channel number (measurement/

computation/external input channel)

p3

Last channel number (measurement/

computation/external input channel)

Example

Output the setting commands setup data of
channels 001 to 005 from the MV.
FE0,001,005

Description • Set the first channel number and last channel

number parameters so that the last channel
number is greater than or equal to the first
channel number.

• Parameters p2 and p3 are valid when p1 is set

to 0, 1, 2, 5, or 6. All channels are specified if
parameters p2 and p3 are omitted.

• Set parameters p2 and p3 according to the

table in section 4.3.

FD

Transmits most recent

measured/computed data

Syntax

FD p1,p2,p3<terminator>
p1

Output data type

0

Output the most recent measured/
computed/external input data in
ASCII format

1

Output the most recent measured/
computed/external input data in
binary format

6

Output relay status and internal
switch status

p2

First channel number (measurement/

computation/external input channel)

p3

Last channel number (measurement/

computation/external input channel)

Example

Output from the MV the most recent measured/
computed data of channels 001 to 005 in ASCII
format.
FD0,001,005

4.7 Output Commands (Control)/4.8 Output Commands (Setting/Measured/Computed Data Output)