Yokogawa Button Operated MV2000 User Manual

Page 48

Advertising
background image

M-4662

2-34

Reading Data into External Input Channels (RD-MV2000 only)

The MV reads the data from the server device and enters the data into external input
channels in 16-bit signed integer format.

• Example 1

Read a 16-bit unsigned integer value from instrument C’s register 30001 into external

input channel 201.

30001

201

16-bit unsigned integer

External input channel

Instrument C register

Command

R

201 - 201

3

30001

UINT16

• Example 2

Read a 32-bit unsigned integer value from instrument C’s register 32001 and 32002

into external input channel 202. Specify the smaller register number in the command.

32-bit unsigned integer

32001

32002

202

External input channel

Instrument C register

Higher bytes
Lower bytes

Command

R

202 - 202

3

32001

UINT32 _ B

Writing Measured Values to a Server
• Example

Write the measured value of channel 1 (16-bit signed integer) to instrument A’s

register 40001.

16-bit signed integer

Measurement channel

Instrument A register

001

40001

Command

W

001 - 001

1

40001

INT16

Writing Computed Values to a Server
• Example

Write the computed value of channel 101 (32-bit signed integer) to instrument A’s

40001 and 40002 registers, lower 16 bits first and then higher 16 bits. Specify the
smaller register number in the command.

32-bit signed integer

Computation channel

Instrument A register

101

Lower bytes
Higher bytes

40001
40002

Command

W-R

101 - 101

1

40001

INT32_L

2.9 Reading/Writing Data on Another Device from the MV via Modbus