Configuring the rd-mv1000 client (modbus client) – Yokogawa Button Operated MV2000 User Manual

Page 56

Advertising
background image

M-4662

2-42

Configuring the RD-MV1000 Client (Modbus client)

The description below assumes that settings other than destination server settings and
commands are at default values.

Registering the Destination Server

The example below describes the settings used to register the RD-MV1000 server to
number 1.
The RD-MV1000 server IP address is assumed to be 192.168.1.101.
◊ Press MENU and then select Menu tab > Basic setting mode > Menu tab >

Communication (Ethernet) > Modbus client > Modbus server settings

Parameter

Setting

Port

502

Modbus server name

192.168.1.101

Unit

Auto

Setting Transmission Commands

◊ Press MENU and then select Menu tab > Basic setting mode > Menu tab >

Communication (Ethernet) > Modbus client > Command settings

Parameter

Setting

Command type

R-M

First and Last

C01

Server

1

Regi.

30001

Type

INT16

2.10 Usage Example of the Modbus Function

Advertising
This manual is related to the following products: