Configured Alarm Information Data

• The MV returns configured alarm information data in response to an FE6 command.
• The ID number of the output format is 26.
• The figure below indicates the format.

Number of blocks

Block size

Configured alarm information block 1

...

Configured alarm information block n

(Reserved) (Reserved)

2 bytes

1 byte

1 byte

1 byte

1 byte

Version (Reserved)

2 bytes

Format Details

Item

Description

Output Value

Version

Format version

1

Number of blocks

*

Number of configured alarm information blocks

Up to 348

Block size

*

Size of the of configured alarm information blocks

24

Block 1 to n

Configured alarm information blocks

Up to 8352 bytes

See Block Details.

* Returned in the byte order specified by the BO command.

Block Details

Item

Number of Bytes

Notes

Channel number

*

2

1 to 440

Decimal place

1

0 to 4

(Reserved)

1

0

Alarm type

4

The following settings are entered in order from
level 1 to 4.

0: Setting off, 1: H (high limit), 2: L (low limit),
3: h (difference high limit),4: l (difference low limit),
5: R (high limit on rate-of-change),
6: r (low limit on rate-of-change),

7: T (delay high limit), 8: t (delay low limit)

Alarm value

*

4×4

The alarm values are entered in order from level 1
to 4.

* Returned in the byte order specified by the BO command.

Manually Sampled Data

• The MV returns the manually sampled data in response to the ME or MO command.
• The ID number of the output format is 17. See section 5.1 for details.
• For the data format, see the RD-MV1000/RD-MV2000 User’s Manual (IM RD-

MV1000-01E).

Report Data

• The MV returns the report data in response to the ME or MO command.
• The ID number of the output format is 18. See section 5.1 for details.
• For the data format, see the RD-MV1000/RD-MV2000 User’s Manual (IM RD-

MV1000-01E).

Display Data (Text)

• The MV returns the display data in response to an ME command.
• The ID number of the output format is 29. See section 5.1 for details.
• For the data format, see the RD-MV1000/RD-MV2000 User’s Manual (IM RD-

MV1000-01E).

Event Data (Text)

• The MV returns the display data in response to an ME command.

5.3 Binary Data Output Format