App index, Web operation log – Yokogawa Button Operated MV2000 User Manual

Page 131

Advertising
background image

5-13

M-4662

Responses

1

2

3

4

5

6

7

App

Index

xxxxxxxxxx

Returns a login history left-justified.

Login:

Login

Logout:

Logout

NewTime:

New time

TimeChg:

Time change

PowerOff:

Power Off

PowerOn:

Power On

TRevStart:

Start of gradual time adjustment

TRevEnd:

End of gradual time adjustment

TimeDST:

Switching of the daylight savings time

SNTPtimset:

Time change by SNTP

nnn

Operation property
KEY:

Key operation

COM:

Communication

REM:

Remote

ACT:

Event action

SYS:

System

uuu···u

User name (up to 20 characters)

_

Space

• Example

EA
99/05/11 12:20:00 Login KEY administrator
99/05/11 12:30:00 Logout KEY administrator
99/05/11 12:20:00 Login COM user
99/05/11 12:30:00 Logout COM user
EN

Web Operation Log

• The MV returns the log of operations on the Web screen in response to an FL

command.

• The MV retains a maximum of 50 operations. Logs that exceed 50 are cleared from

the oldest ones.

Syntax

EACRLF
yy/mo/dd_hh:mm:ss_ffffff_eee_???···?CRLF
···································
ENCRLF

yy

Year (00 to 99)

mo

Month (01 to 12)

dd

Day (01 to 31)

hh

Hour (00 to 23)

mm

Minute (00 to 59)

ss

Second (00 to 59)

ffffff

Requested operation

SCREEN:

Screen change

KEY:

Key operation

MSG:

Message assignment/write

CREATE:

File generation

5.2 Text Data Output Format

Advertising
This manual is related to the following products: