Trouble shooting, Test process, Recovery process – MAHLE RTI RHS700 User Manual

Page 19: Problem fault remedy

Advertising
background image

- 10.1 -



Trouble shooting



C:\RHS Computer Files\Instructions\RHS\GB\645-40\0009A-01.doc 1997.03.26
RHS 700

Test process


Problem Fault

Remedy

Pressure gauge shows no
pressure

1. + 2. Valve not opened




3. No refrigerant in A/C unit

1. Open high and low-pressure valves on service

couplings


2. Open valves on service couplings

3. Repair A/C unit

Pressure gauge shows
the same reading all the
time

1. A/C unit defective

2. A/C unit not cut in

1. Empty A/C unit and repair

2. Cut in A/C unit


Recovery process:


Problem Fault

Remedy

Recovery process does
not start - green recovery
lamp does not light up

1. RHS 700 not cut in

2. Valves not opened


3. No refrigerant in A/C unit

4. System pressure is 16 bar

5. Internal cylinder full

6. Internal component fault

1. Cut in RHS 700

2. Open high and low-pressure valves on

service couplings


3. Repair A/C unit

4. Contact RHS 700 supplier

5. Empty cylinder

6. Contact RHS 700 supplier

Recovery process does
not stop

1. Oil drain valve not closed

2. A/C unit leakage

3. Internal component fault

1. Close valve

2. Contact RHS 700 supplier

3. Contact RHS 700 supplier

Recovery process runs
only for a short period

1. Valves on service couplings not opened

2. System pressure is 16 bar

3. Internal cylinder full

4. Internal component fault

1. Open valves

2. Blow off non-condensable gases

3. Empty cylinder

4. Contact RHS 700 supplier