- 15.2 -


Appendixes



C:\RHS Computer Files\Instructions\RHS\GB\645-40\0009A-01.doc 1997.03.26
RHS 700

Test 1:

High pressure

8 - 9 bar

Low pressure

Approx. 0.8 bar

Fault/problem

Symptom

Possible cause

Remedy

Unsatisfactory
refrigeration output

Virgin ventilation air

Air bubbles in sight
glass

Leak in A/C unit

Insufficient refrigerant
in A/C unit

Locate leak and repair

Replenish refrigerant



Test 2:

High pressure

Approx. 20 bar

Low pressure

Approx. 2.5 bar

Fault/problem

Symptom

Possible cause

Remedy

Unsatisfactory
refrigeration output

Refrigerant

over-

charged

Insufficient condenser
cooling

Fan not running

Reduced condenser
output because of oil
or dirt deposits

Insufficient oil in A/C
unit (compressor fric-
tion)




Clean the condenser


Repair fan

Clean the condenser



Replenish oil

If none of the above
steps remedy the fault,
check refrigerant
quantity in A/C unit,
empty, evacuate and
recharge unit