- 15.4 -


Appendixes



C:\RHS Computer Files\Instructions\RHS\GB\645-40\0009A-01.doc 1997.03.26
RHS 700

Test 5:

High pressure

Approx. 19 - 20 bar

Low pressure

Approx. 2.5 bar

Fault/problem

Symptom

Possible cause

Remedy

Unacceptable cooling

Ice or moisture on
hoses on high and low-
pressure sides of A/C
unit

Expansion valve
defective or sensor
placed incorrectly

Expansion valve opens
too much

Check position of
expansion valve
sensor.

Replace expansion
valve.



Test 6:

High pressure

Approx. 7 - 10 bar

Low pressure

Approx. 4 - 6 bar

Fault/problem

Symptom

Possible cause

Remedy

A/C unit does not cool Pressure on low-pres-

sure side too high or
pressure on high-pres-
sure side too low

Internal compressor
leakage

Repair or replace com-
pressor