Appendixes – MAHLE RTI RHS700 User Manual

Page 29

Advertising
background image

- 15.1 -


Appendixes



C:\RHS Computer Files\Instructions\RHS\GB\645-40\0009A-01.doc 1997.03.26
RHS 700

Example of trouble shooting on an A/C unit:

Conditions:


1.

Ambient temperature

30-35°C (86-95°F)


2.

Motor

speed

2,000

rpm


3.

A/C unit temperature setting

Maximum



Under the above conditions an intact A/C unit will show the following
pressures in the TEST process:


High

pressure

15

bar


Low

pressure

2

bar



Follow the TEST process as shown in section 5:

-

Connect service couplings to the A/C unit.


-

Close the high and low-pressure valves on RHS 700


-

Open the valves on the service couplings.


-

Cut in the A/C unit.


-

The station will now perform a test function.

Perform a condition diagnosis in accordance with the supplier’s instructions.


-

When the test is completed, cut the A/C unit off again.