These are the ASCII characters needed when working with the EMO-1005

ASCII Decimal ASCII Decimal

0 48

A 65

1 49

B 66

2 50

C 67

3 51

D 68

4 52

E 69

5 53

F 70

6 54
7 55

J

74

8 56

K 75

9 57


BASIC PROGRAM FOR TESTING THE SERIAL PORT.

The BASIC program below will help test the communication port with a IBM PC compatible

computer. The program can be used in connection with BASIC, BASICA, GWBASIC or any other

reasonably standard PC BASIC.

10 REM *** EMO-1005 Serial port test program --------------

20 REM

30 OPEN "COM1:9600,N,8,1,RS,CS,DS,CD" AS #1

40 REM 9600 baud/no parity/8 data bits/1 stop bit/no hand shakes

50 INPUT "Enter string to send ",T$

60 REM for example 01K006304. This will read Totalizer channel 1

70 REM the > sign and carriage return is added later in the

80 REM program.

90 REM the next 4 lines calculates the checksum

100 FOR X=1 to LEN(T$)

110 NUM=NUM+ASC(MID$(T$,X,1))

120 NEXT X

130 CHK$=HEX$(NUM-(FIX(NUM/256)*256))

140 REM CHK$ carries the checksum as a string

150 REM now send the message

160 PRINT#1,;">";T$;CHK$;CHR$(13)

170 REM and print the message on screen

180 PRINT "Sent : ";">";T$;CHK$;CHR$(13)

190 PRINT "Waiting for replay........"

200 LINE INPUT#1,X$

210 PRINT "Received : ";X$;CHR$(13)

220 CLOSE #1

230 END

Before running the program make sure all hardware aspects are OK and the EMO-1005 is hooked up

correctly.