Specifications – Edwards Signaling ReadySet User Manual

Page 15

Advertising
background image

Chapter 2: Product description

ReadySET Aspirating Smoke Detection System Installers Handbook

7

Specifications

Caution:

This equipment is only to be used in accordance with this specification.

Failure to operate the equipment as specified may cause damage to the unit, injury, or
property damage.

Specification Value

Supply voltage

22.25 - 26.40 VDC

Current consumption

350 mA

Dimensions

7.5 W x 9.0 H × 4.3 D (in.) 190 W × 230 H × 110 D
(mm)

Weight

2.65 lbs. (1.2 kg)

Operating temperature range

32 to 100°F (0 to 38°C) (UL 268 compliance)

Operating humidity range

0 to 90% noncondensing

Coverage area

2,500 sq. ft. (232 sq. m)

Sensitivity range
(%obs/ft.)
(%obs/m)

Min. = 7.62%, Max. = 0.122% FSD
Min. = 25%, Max. = 0.4% FSD

Maximum sensitivity resolution

0.12% obs/ft. (0.4% obs/m)

Preengineered piping sample hole

0.5% to 1.5% obs/ft. (1.64% to 4.92% obs/m)

Detection principle

Laser light scattering mass detection

Particle sensitivity range

0.0003

t

m to 10

t

m

Relay contact rating

1 A at 24 VDC resistive load

Sampling pipe inlets

1

Sampling pipe internal diameter

3/4-inch (20 mm)

Relay outputs

Alarm, Pre-Alarm, and Fault

Chamber service intervals

Greater than 8 years (depending on environment)

Dust separator (filter) replacement intervals Greater than 5 years (depending on environment)

Laser lifetime (MTTF)

Greater than 1,000 years

Programming

Internal DIP switches

APIC compatible

Yes

Enclosure NEMA-1

Advertising