Indicators – Edwards Signaling ReadySet User Manual

Page 16

Advertising
background image

Chapter 2: Product description

8

ReadySET Aspirating Smoke Detection System Installers Handbook

Indicators

Figure 1 below shows the seven indicators on a ReadySET detector.

Figure 1: ReadySET detector indicators

(1)

ALARM:

Illuminates to indicate that the smoke level has passed the detector’s Fire 1 threshold, and

the normally open ALARM relay contacts have closed.

(2)

PRE-ALARM:

Illuminates to indicate that the smoke level has passed the detector’s Pre-Alarm

threshold, and the normally open PRE-ALARM relay contacts have closed.

(3)

FAULT:

Illuminates to indicate a fault condition and that the normally closed FAULT relay contacts

have opened. Three additional LEDs indicate the type of fault.

(4)

OK:

Illuminates to show normal operation when there are no faults. The OK lamp will flash during

the 15-minute FastLearn period when the detector is first learning about its environment.

Note:

During initial setup, the OK LED will flash for 15 minutes while the detector learns its operating

environment. This does not indicate a problem with the detector.

Advertising