Chapter 3: Installation and configuration
26
ReadySET Aspirating Smoke Detection System Installers Handbook
Figure 12: DIP switch
Table 3: DIP switch settings
Setting Switch
1
Switch
2
Switch
3
Switch
4
Switch
5
Switch
6
Switch
7
Switch
8
Set detector
sensitivity
Alarm factor 6
OFF OFF
Alarm
factor
7
ON
OFF
Alarm
factor
8
OFF
ON
Alarm
factor
9
ON
ON
Classifire On
OFF
Fixed alarms
ON
Flow limit offset
±40
OFF
OFF
±20
ON
OFF
±5
OFF
ON
±3
ON
ON
Flow delay
240
seconds
OFF
30
seconds ON
Input select
Psu
fault OFF
Classifire
Override
ON
Auto calibration
Enable
OFF
Disable
ON
Note:
The settings in bold text are the factory default settings.