Sample pipe networks – Edwards Signaling ReadySet User Manual

Page 22

Advertising
background image

Chapter 3: Installation and configuration

14

ReadySET Aspirating Smoke Detection System Installers Handbook

Sample pipe networks

Simple designs with short sampling pipes produce the best results. Maximum allowed
sampling pipe length is 164 feet (50 meters) in still air. In areas or applications where
the external airflow rate is greater than 3 feet per second (1 meter per second), the
maximum sampling pipe length is reduced to 33 feet (10 meters).

Figure 3: Sample pipe network

ReadySET

detector

ReadySET

detector

10 ft. or greater

Two branched pipe sampling network

Single pipe sampling network

10 ft. or greater

Advertising