24

Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010

Product Description

Getting Started

1.7.1 ACC-25/50 With ACC-25/50DA(s), System Requiring More

Than 50 Watts of Audio Power

Connect the Audio Riser and Master Command Bus (for All-Call) cabling between the ACC-
25/50 and ACC-25/50DA panels. Refer to Section 5, 'Application Examples' on page 59.

Install backboxes and circuit boards as described in Section 3, 'Installation' on page 33.

Configure the ACC-25/50 for Single Zone operation using DIP switch S3 switches 1, 2 and 3
on the ACC-MCB motherboard. Refer to Section 2, ‘Field Programming’ in the ACC-25/50
Series Manual. The ACC-25/50DA DIP switches can be left at the default settings.

If the optional message generator is installed, record any new voice messages as described in
Section 4, 'Operating Instructions' on page 52.

1.7.2 ACC-25/50ZS/T With ACC-25/50DAZS, System Requiring

More Than 50 Watts of Audio Power

Connect the Audio Riser and EIA-485 cabling between the ACC-25/50ZS/T and
ACC-25/50DAZS panels. Refer to Section 5, 'Application Examples' on page 59.

Install backboxes and circuit boards as described in Section 3, 'Installation' on page 33.

Configure the ACC-ZPMK on the ACC-25/50ZS with the number of ACC-25/50DAZS panels
connected on the Zone System serial link.

Configure the address wheel located on the ACC-ZPM in the ACC-25/50DAZS panel.

If the optional message generator is installed, record any new voice messages as described in
Section 4, “Operating Instructions”, on page 52.