4 auxiliary dc power output connections, 5 input circuits, 1 master command bus – Fire-Lite ACC-25/50DAZS Distributed Audio Panel User Manual

Page 39: Master command bus

Advertising
background image

Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010

39

Auxiliary DC Power Output Connections

Installation

3.4 Auxiliary DC Power Output Connections

The Special Application Auxiliary DC power output (35 mA @ 24 VDC) is power-limited, nonret-
table power suitable for powering control modules and End-of Line Power supervision relays. See
the Device Compatibility Document for compatible devices.

3.5 Input Circuits

3.5.1 Master Command Bus

The Master Command Bus Input circuit, when used with the ACC-25/50 Series, can be used to add
paging flexibility. All field wiring for each circuit is power-limited and supervised for opens and
ground faults. Note that zero impedance to ground will be indicated as a ground fault.

The Master Command Bus Input circuit is triggered by a reverse polarity signal such as the one
from the Master Command Output Bus on the ACC-25/50 Series. Master Command input and out-
put terminals are provided to allow connection to additional audio distribution panels.

When connecting the Master Command Output of ACC-25/50 Series to the Master Command Bus
Input of distributed audio panels, the wiring must be supervised by a 4.7K EOL resistor connected
across the out terminals of Master Command Bus Output on the last panel.

In Example 1 illustrated below, the Master Command bus is activated during paging, which routes
paging audio from the riser to the Distributed Audio Panel speakers.

The maximum line resistance from the main ACC-25/50 Series to the last Distributed Audio Panel
is 130 ohms (65 ohms per conductor).

Figure 3.6 Auxiliary Power Connection

acc25d

at

b9.

wm

f

Figure 3.7 Example 1 - Activating Multiple Distributed Audio Panels with Master CMD Output Bus

VECP ELR

(Paging active polarities shown)

General or

Emergency All-

Call Paging

Master Command

Bus

Master Command

Bus

Master

CMD

Output

Bus

Voice Evacuation

Control Panel

(VECP)

Distributed Audio Panel

Distributed Audio Panel

acc25

5

0dou

t.wmf

ACC-AAM25

audio
riser

audio riser

ACC-AAM25

ELR

NOTE:

The ACC-25/50DAZS uses the Zone System serial link for paging operations, therefore

Master Command Bus connections are only used with ACC-25/50DA panels.

Advertising
This manual is related to the following products: