Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010

Field Programming

Switch SW1 Settings on Optional FC-MGM Module

Switch 6, 7 and 8 - used to determine the number of times the voice message will repeat.

SW2 - Record Bypass Switch (on optional FC-MGM Module)

This switch, when placed in the down position, prevents accidental erasure of stored voice mes-
sages. See 'Operating Instructions' on page 52 for additional information.

•UP Position = The stored digital voice message may be overwritten with
a new one.
•Down Position = The stored digital voice message can not be
overwritten (factory default setting).

SWITCH

6

SWITCH

7

SWITCH

8

NUMBER OF TIMES TO REPEAT DIGITAL

VOICE MESSAGE

ON

OFF

OFF

3

OFF

ON

OFF

3

ON

ON

OFF

6 (factory default)

OFF

OFF

ON

8

ON

ON

ON

INFINITE (until FACP trigger is reset)

Table 2.4 Switch Settings for Message Repeat