Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010

41

Output Circuits

Installation

3.6 Output Circuits

3.6.1 Trouble Relay - TB1

The main circuit board provides a Form-C Trouble relay, for independent monitoring, rated for 2.0
amps @ 30 VDC (resistive) and 0.6 amp @ 30 VAC (resistive). This relay is ‘fail safe’, meaning
that it is normally energized. Should system power shut off, this relay will deenergize, transferring
its contacts.

3.6.2 AC Power Loss Relay - TB11

The main circuit board provides a Form-C AC Power Loss relay rated for 2.0 amps @ 30 VDC
(resistive) and 0.6 amps @ 30 VAC (resistive).

ac2

5

da

tb

12

.wmf

Remote Power Supply

or Battery Charger

Normally Open

Contacts

1 2

Figure 3.9 Trouble Contact Input Terminal

Figure 3.10 Trouble Relay

TB1

25

50

daa

cr

l.w

m

f

Shown in energized,
nontrouble condition

Figure 3.11 AC Power Loss Relay

TB11

Shown in energized,

normal AC Power condition

25

50

da

acr

l.w

mf