2 playback button, Playback button – Fire-Lite ACC-25/50DAZS Distributed Audio Panel User Manual

Page 53

Advertising
background image

Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010

53

Playback Button

Operating Instructions

6. Note the following while recording:

• During the message selection process, the Record LED will repeat a flash rate in the

following manner:

– Initial Record button press to select message #1 - ¼ second flash rate
– Press Record button a 2nd time to select message #2 - two ¼ second flashes
– Press Record button a 3rd time to select message #3 - three ¼ second flashes
– Press Record button a 4th time to select message #4 - four ¼ second flashes
– Press Record button a 5th time extinguishes the Record LED and terminates the record

process

– The total flash interval time is 9 seconds

To alert the user that there is only two seconds of record time remaining, the LED on the
Record button will change from steady-on to flashing.
• The System Trouble LED and Trouble Relay will be on while recording. The system will

not respond to CMD inputs or Zone System serial link controls from the ACC-25/50ZS/T
while recording.

• It is not necessary to fill the entire record time. The time limits represent the maximum time

allotted.

• Factory default messages are replaced with the custom message recordings from the

External Audio Input Jacks or microphone.

7. Press the button labeled ‘Record’ the respective number of times to select the appropriate

message to record as described in Step 6. The Record LED will flash as described above.
After 9 seconds, the Record LED will switch to steady on, at which point the recording of the
voice message may commence.

8. At the end of recording, the Record button must be pressed again to signal the end of the

recorded message. Avoid long pauses at the end of the message by promptly pressing the
Record button when the voice message input has stopped. Note that it is not necessary to fill
the entire 60 second record time. The time limit represents the maximum time allotted. If the
Record button is not pressed to signal the end of the voice recording, the unit automatically
ends the message at the time out period.

9. Disable recording by setting SW1 switch 3 to the OFF position.
10. Playback the recorded messages for accuracy. This may be done via the ‘Playback’ key or by

creating an alarm or evacuate condition. The Playback feature allows for reviewing the
message locally via the FC-LPS option module without generating the message through the
amplifiers.

4.2 Playback Button

The Playback button can be used to review the stored voice message. By connecting the optional
Local Playback Speaker Module (FC-LPS), the message can be heard without transmitting it over
the system speakers.

Message Playback
1. Control the Message Control Settings on S1 DIP switches 7 and 8 located on the Distributed

Audio Panel motherboard. These settings will determine the number of messages that can be
played-back. Table 2.2 on page 27.

!

CAUTION:

OBSERVE SWITCH POSITION

BE CERTAIN TO SLIDE THE RECORD BYPASS SWITCH SW2 TO THE DOWN POSITION WHEN
RECORDING IS COMPLETED. THIS WILL PREVENT ACCIDENTAL RERECORDING OR
DELETION OF THE STORED MESSAGE. IT IS NOT POSSIBLE TO RECORD WITH THE SW2
RECORD BYPASS SWITCH IN THE DOWN POSITION.

Advertising
This manual is related to the following products: