Iii - 3.1. configuration, Iii - 3.1, Ipdact-ud - configuration – Fire-Lite IPDACT-2UD Technical Reference User Manual

Page 21: Iii-18

Advertising
background image

IPDACT-UD - Configuration

III-18

Doc.DM385-I

Rev. 2.0

return to the start. If the password is incorrect, the telephonic console will
automatically deactivate and return to the initial position; if the relays are
inactive then you return to the initial position.

If at any point you hang up the phone, the telephonic console deactivates.

III - 3.1. Configuration

Configuring the various parameters is carried out through the access and
register writing. A register is used for each parameter to be configured. Each
register is made up of one or various fields. The number of fields and size of
each depends on the type of register. All the fields pertaining to one register
have the same size. In order to access a register, press * and the two digits
corresponding to the register to be configured. After selecting a register you
will hear a simple beep indicating that this register can be configured. From
this point you can configure the first field in the register. Should you select an
invalid register, an error signal is emitted. This consists of a long tone.

The access process for a register can be terminated at any point using the
escape sequence *# (asterisk, pound). In this case an escape signal is
emitted which consists of three short tones.

The available configuration registers are as follows:

Types of register

registe

r

fields

Field size

Default value

IPDACT-UD IP address and mask

01

8

(3+1)

192.168.000.100
255.255.255.000

IPDACT-UD access gateway

02

4

(3+1)

192.168.000.200

Access password for the console

03

2

Variable, max. 16
characters, these must be
the same.

24680

Remote configuration request

04

1

Variable

None

IPDACT-UD Reset

05

1

Variable

N/A

IPDACT-UD account number

11

1

(8+1)

000000

Visor Alarm IP address

12

4

(3+1)

None

UDP port

13

1

(5+1)

00080

IPDACT-UD message encryption

key

14

2

Variable, max. 16
characters, these must be
the same.

None

VisorAlarm message encryption

key

15

2

Variable, max. 16
characters, these must be
the same.

None

Interval between keep-alive (sec)

16 1

(5+1)

00010

Retries after failed keep-alive

17 1

(1+1)

3

Time between retries for sending

keep-alives (sec).

18 1

(1+1)

3

Number of digits for a telephone

number.

19 1

(2+1)

09

Retries for sending an alarm

20

1

(1+1)

5