IPDACT-UD - Configuration

III-24

Doc.DM385-I

Rev. 2.0

This is the IP address that the backup VisorALARM IP receiver has, which
receives both monitoring traffic as well as traffic corresponding to the alarms
generated by the control panel in cases where the main VisorALARM fails.

The register is made up of 4 fields, corresponding to the 4 numbers in the IP
address; this admits values between 0 and 255. Each number has a
verification digit for this. Default is:

000

000

000

000

Interval between backup keep-alives (seconds)

Time period where the IPDACT-UD executes a check on connectivity with the
backup Teldat VisorALARM. To do this, the IPDACT-UD sends a keep-alive
frame and waits for a response from the IP receiver.

The register is made up of a 5-digit field. The interval is expressed in seconds
and admits values between 00000 and 90 seconds. The field contains one
verification digit for the number. Default value is 00010.

Retries after failed keep-alives to backup

If the IPDACT-UD, on checking connectivity with the backup Teldat
VisorALARM, does not receive a response to this within “interval-between-
retries-to-send-keep-alives
” seconds, the IPDACT-UD repeats the keep-alive
sending process. If there is no response within the same time interval, the
sending process is repeated and so on until the configured number of sending
times in this register has been completed. After this number of configured
retries, the connection with the Teldat VisorALARM is considered down and
the control panel subsequently accesses the telephone network.

The register is made up of one 1-digit field. This admits values between 1 and
9. Default value is 3.

Interval between retries to send keep-alives (seconds) for the backup

Time interval between sending keep-alive frames when a possible
connectivity problem with the backup VisorALARM IP receiver has been
detected.

The register consists of one 1-digit field. This is expressed in seconds and
admits values between 3 and 9.

This field contains one verification digit for the number. Default value is 3.

Number of digits for a telephone number

This is the number of digits containing the telephone number which the control
panel must dial to carry out a call. Depending on the country, if there is a
switchboard, etc.