Appendix c: nfpa standard-specific requirements – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual

Page 126

Advertising
background image

126

MRP-2001 Series Manual — P/N 53040:D 12/15/2010

Appendix C: NFPA Standard-Specific Requirements

This panel has been designed for use in commercial, industrial and institutional applications and
meets the requirements for service under the National Fire Protection Association (NFPA)
Standards outlined in this Appendix. The minimum system components required for compliance
with the appropriate NFPA standard are listed below:

MRP-2001 Control Panel

Contains the main control board, cabinet (backbox and door) and power supply.

Batteries

Refer to “Power Supply Calculations” on page 101, for Standby Power Requirements.

Initiating Devices

Connected to one of the control panel's Initiating Device Circuits.

Notification Appliances

Connected to one of the control panel's Output Circuits.

Releasing Devices

Connected to one of the control panel's Output Circuits.

The following additional equipment is needed for compliance with the NFPA 72 standards listed
below:

NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station
Service

411UD may be installed as illustrated in Figure C.1, “FACP Connection to 411UD,” on page
127
OR
4XTMF Transmitter Module for connection to the RS82 Remote Station Receiver. See Figure
C.3 on page 130, for in
stallation instructions for this unit

NFPA 72 Auxiliary Fire Alarm System

4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
This unit must be installed as illustrated in the section titled “4XTMF Municipal Box Transmitter
Option Module” on page 31
and as outlined in Figure C.2, “Municipal Box Connected to 4XTMF
Transmitter Module,” on page 129.

NFPA 72 Proprietary Fire Alarm System

FACP Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.4,
“Proprietary Protective Signaling System,” on page 131, fo
r installation instructions for this unit.

The relay contacts of this control panel may be used to trip any dialer that is UL-listed for Central
Station/Remote Station services. The illustrations in this appendix provide examples of possible
system configurations.

Advertising
This manual is related to the following products: