Page 37: Installation, Specifications installation

Advertising
background image

MRP-2001 Series Manual — P/N 53040:D 12/15/2010

37

ANN-BUS Devices

Installation

2.7.2 ANN-BUS Device Addressing

Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled “ANN-BUS” on page 73).

A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.

2.7.3 ANN-80 Remote LCD Annunciator

The ANN-80 LCD Annunciator is a compact, 80 character, backlit LCD remote fire annunciator
which mimics the FACP display. It also provides system status indicators for AC Power, Alarm,
Trouble, Supervisory and Alarm Silenced conditions. Communication between the ANN-80 and
FACP is accomplished over a two wire serial interface employing the ANN-BUS communication
format. The devices are powered, via two additional wires, from either the host FACP or remote
UL-listed, filtered, power supply.

Specifications

Operating Voltage Range: 18 VDC to 28 VDC

Current Consumption @ 24 VDC nominal (filtered and nonresettable):

Normal/Standby (no activity): 37.0 mA

Trouble: 39.0 mA

Alarm: 40.0 mA

AC Fail (not backlit): 15.0 mA

For use indoors in a dry location

Installation

Ensure that all power (AC and DC) has been removed from the FACP before installing the
annunciator.

Mounting

The ANN-80 can be surface mounted using the optional ANN-SB80KIT-R (red) or
ANN-SB80KIT-W (white) surface mounting box or semi-flush mounted to a single, double or 4”
square electrical box. Select and remove the appropriate knockout(s), pull the necessary wires
through the knockouts and mount the annunciator in or on the wall depending on the type of
installation desired.

NOTE: address (ID Number) DIP switches on some devices may have more than 5 switch
positions. Unless otherwise specified in the documentation supplied with each device, switch
positions 6 and above must be set to OFF.

Address

Switch 5

Switch 4

Switch 3

Switch 2

Switch 1

not valid

OFF

OFF

OFF

OFF

OFF

01

OFF

OFF

OFF

OFF

ON

02

OFF

OFF

OFF

ON

OFF

03

OFF

OFF

OFF

ON

ON

04

OFF

OFF

ON

OFF

OFF

05

OFF

OFF

ON

OFF

ON

06

OFF

OFF

ON

ON

OFF

07

OFF

OFF

ON

ON

ON

08

OFF

ON

OFF

OFF

OFF