Timers, System setup 1=future use 2=timers 3=banner, Timers 1=ac loss delay 2 hr – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual

Page 67

Advertising
background image

MRP-2001 Series Manual — P/N 53040:D 12/15/2010

67

Master Programming Level

Programming

Pressing 3 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:

Timers

Timers for Soak, Waterflow Delay and AC Loss Delay can be programmed by pressing 2 while
viewing System Setup Screen #1. The following screen will be displayed:

PROGRAMMING

1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETUP

Programming Screen

SYSTEM SETUP
1=FUTURE USE
2=TIMERS
3=BANNER

System Setup Screen #1

SYSTEM SETUP
1=TIME-DATE
2=TROUBLE REMIND NO
3=CHARGR DISABLE NO

System Setup Screen #2

SYSTEM SETUP
1=CANADIAN OPTION OFF
2=SEC ANN ENABLE NO

System Setup Screen #3

SYSTEM SETUP

1=FUTURE USE
2=TIMERS
3=BANNER

System Setup Screen #1

TIMERS
1=SOAK 1 10 MIN
2=SOAK 2 10 MIN
3=WATERFLOW DELAY 60S

Timer Screen #1

TIMERS
1=AC LOSS DELAY 2 HR

Timer Screen #2