Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual

Page 132

Advertising
background image

132

MRP-2001 Series Manual — P/N 53040:D 12/15/2010

NFPA Standard-Specific Requirements

Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts

C.2 Central Station/Remote Station Transmitter: Connection

to FACP Dry Contacts

The dry contacts of the MRP-2001 programmable relays can be used to trip a UL-864 Listed
Central Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central
Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value
determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote
Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter
manufacturer’s manual for details.

Figure C.5 FACP Dry Contacts Connection to Central Station/Remote

Station Transmitter

Typical Central Station/Remote Station Transmitter Module

Typical Input Zone Triggers

Fire Alarm Control Panel

Alarm

Sup

erv

.

T

roub

le*

*Note: The Trouble Relay is a
fail-safe relay. With power
applied to the FACP and no
troubles in the panel, the wiring
should be connected to the NO
and C contacts as indicated in the
illustration.

rp

20

02

d

ry

sm

it.

cdr

Advertising
This manual is related to the following products: