MRP-2001 Series Manual — P/N 53040:D 12/15/2010

Installation

Input Circuits

2.3 Input Circuits

The MRP-2001 has six programmable IDCs (Initiating Device Circuits). Each circuit is compatible
with System Sensor’s i

3

smoke detectors which generate a maintenance signal when the detector

becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the
detector rating of approximately 45

o

F. The maximum loop resistance limit for each IDC is 100

ohms (700 ohms for linear heat detection). Do not use 2-wire smoke detectors on input zones used
for linear heat detection. The field wiring for each zone is supervised for opens, shorts and ground
faults. All conditions are visually and audibly annunciated.

Each circuit is configured for Style B (Class B) operation and will accept i

3

smoke detectors, any

normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors.
Refer to the Device Compatibility Document for a list of compatible devices.

Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A
Converter module. Refer to “CAC-5X Class A Converter Module” on page 29.

Figure 2.5 IDC Connections

Class B Initiating Device Circuits (supervised and power-limited) 4.7 K

, ½ watt resistor P/N:71252

manual pull stations

heat detectors

Dummy load all unused

circuits - 4.7 K

, ½ watt

resistor (P/N: 71245)

mr

p-

20

01

id

c.

cd

r

UL listed Power Supervision Relay

(refer to Device Compatibility Document for list of compatible relays)

Resettable 24 VDC
4-wire smoke
detector power
(500 mA maximum)

UL listed compatible 4-wire smoke detector

manual
release

Input IDC
Waterflow Circuit
Normally Open
Waterflow Devices
or Pressure
Switches