Measurement – KYORITSU 3023 User Manual

Page 12

Advertising
background image

6-1 Voltage measurement (Mains disconnection check)

(1) Connect the Earth probe to the earth of the circuit under test and

Line probe to the other side. If the circuit is not earthed, connect

Earth probe to any appropriate conductor.

(2) Take the reading on the LCD without pressing the Test button or

Remote control switch. The mark "∼" is displayed when

measuring AC voltage. The mark "− (minus)" is displayed when

the LINE probe is connected to the negative side of the conductor

under test to measure DC voltage. "Lo" is displayed on the LCD

when the measured voltage is under 20V.

DANGER

¡

Test lead and fuse must be inspected prior to measurement

according to Clause 5-2 indicated in this manual in order to avoid

possible electrical shock hazard. Voltage cannot be measured if a

break is present on the fuse.

¡

Never make measurement on a circuit in which the electrical

potential exceeds AC/DC600V in order to avoid possible shock

hazard. (Refer to "3.Specification, AC voltage measurement.")

¡

When testing installation that has a large current capacity, such as

a power line, be sure to make measurement on the secondary side

of a circuit breaker in order to avoid personal injury.

¡

Do not press the Test button or Remote control switch during

voltage measurement.

¡

Never short live conductors with the tip of a probe to avoid

personal injury.

¡

Do not make measurement with the Battery cover removed.

6-2 Insulation resistance measurement

Before performing any insulation test, check the maximum voltage

that may be applied to the circuit under test.

― 10 ―

6.Measurement

CAUTION

Never press

test button

CAUTION

Never press

remote switcth

Fig. 4