― 14 ―

6-5 Measurement of resistance (Continuity check)

DANGER

¡

Do not apply voltage to the resistance range. Always test the circuit

or equipment to ensure it is surely de-energized before

measurement.

Zero Ω ADJ. function

This is a function to null the resistance of the test lead or fuse in order

to display the resistance of the equipment under test only.

Setting:

(1) Set the Range selector switch to theΩ(Continuity) position.

(2) Short the test leads: LINE (red) and EARTH (black).

(3) Press the Zero Ω ADJ. key with the Test button locked or with the

Remote control switch pressed. Then

mark is lit up and a

value of 0.00 Ω is displayed on the LCD. This value is saved in

the memory of the instrument and won't be cleared after turning

off the instrument.

Fig. 9