KYORITSU 6016 User Manual

Page 33

Advertising
background image

30

Protection by gG fuses

with Uo of 230V

Protection by MCBs with Uo of 230V

(Disconnection time 0.4 and 5s)

Rating

(A)

Disconnection

time 5s

Disconnection

time 0.4s

Characteristic

B

Characteristic

C

Characteristic

D

Ia

(A)

Zs

(Ω)

Ia

(A)

Zs

(Ω)

Ia

(A)

Zs

(Ω)

Ia

(A)

Zs

(Ω)

Ia

(A)

Zs

(Ω)

6

17

13.5

38

8.52

30

7.67

60

3.83

120

1.92

10

31

7.42

45

5.11

50

4.6

100

2.3

200

1.15

16

55

4.18

85

2.7

80

2.87

160

1.44

320

0.72

20

79

2.91

130

1.77

100

2.3

200

1.15

400

0.57

25

100

2.3

160

1.44

125

1.84

250

0.92

500

0.46

32

125

1.84

221

1.04

160

1.44

320

0.72

640

0.36

40

170

1.35

--

--

200

1.15

400

0.57

800

0.29

50

221

1.04

--

--

250

0.92

500

0.46

1000

0.23

63

280

0.82

--

--

315

0.73

630

0.36

1260

0.18

80

403

0.57

--

--

100

548

0.42

--

--

The most complete loop testers or Multifunction testers also have the Prospective Fault
current measurement. In this case, Prospective Fault current measured with instruments
must be higher than the tabulated Ia of the protective device concerned.

Below is a practical example of verification of the protection by MCB in a TN system
according to the international Standard IEC 60364.

L-PE

230

V

50.0Hz

L-PE

L-N

!

ATT:ON

Fig.25

Advertising