9.3. Operating instructions for LOOP and PSC/PFC
9.3.1 Initial Checks: to be carried out before any testing
1. Preparation
Always inspect your test instrument and lead accessories for abnormality or damage:
If abnormal conditions exist DO NOT PROCEED WITH TESTING. Have the instrument
checked by your distributor.

Operation of Function Switch
LOOP

F1

Switches measurement mode:
L-PE or L-N/L-L

F2 ATT setting (on or off)
F3 N/A
F4 N/A

PSC/PFC

F1

Switches measurement mode:
PFC or PSC

F2 ATT setting (on or off)
F3 N/A
F4 N/A

(1) Operate the Power button and turn on the instrument. Turn the Function switch and

set it to either the LOOP or PSC/PFC position.

(2) Insert the Test Lead into the instrument. (Fig.29)

L-PE

ATT : ON

230V

50.0Hz

L-PE

L-N

!

Fig.27

PFC

A

230V

50.0Hz

L-PE

ATT:ON

L-PE

L-N

!

Fig.28

Fig.29