Volts, Touch pad, Back light – KYORITSU 6016 User Manual

Page 49

Advertising
background image

46

13. VOLTS

1. Operate the Power button and turn on the instrument. Turn the rotary switch and

select the VOLTS function.

2. Insert the Test Leads into the instrument. (Fig.47)

3. Voltage value and frequency will be displayed on the LCD when applying AC voltage.
Note : A message “DC V” may be displayed when measuring AC voltages with

frequencies out of the range 45Hz - 65Hz.

14. TOUCH PAD

1. The touch pad measures the potential between the operator and the tester's PE

terminal.

A message “PE HiV” is displayed on the LCD with the audible buzzer if a potential

difference of 100V or more is present between the operator and the PE terminal at
touching the Touch pad.

2. Touch Pad function can be enabled and disabled (ON / OFF); refer to ”6.

Configuration” in this manual and select ON or OFF. In case that OFF is selected, a
warning for “PE HiV” does not appear and the buzzer does not sound.

* Initial value: ON
Note : A message “PE HI V” may be displayed when testing inverters or measuring

voltages containing high frequencies even if a user isn't touching with the Touch Pad.

15. BACK LIGHT

Pressing the Back Light Button selects Backlight ON / OFF. Backlight automatically
turns off in 60 sec after it turns on. Backlight at powering on the instrument can be set
either ON or OFF. Refer to “6. Configuration” in this manual how to select ON / OFF.