Specification – KYORITSU 6201 User Manual

Page 11

Advertising
background image

9

General specification, measuring range and accuracy
Voltage(VOLT) measurement of main power supply

Measurement of Protective conductor resistance(RPE)

Measurement of Insulation resistance (RINS)

Threshold and display

4. Specification

Measuring range
Resolution
Accuracy

207 ~ 264V AC
1V

±

(2%rdg+3dgt)

Measuring range
Resolution
Open-circuit voltage

Measuring current

Accuracy

0 ~ 19.99

Ω

10m

Ω

±

5.0

±

0.4V DC

Within 200 ~ 250mA DC
(when measuring 0 ~ 2

Ω

±

(2%rdg+3dgt)

Rating
Measuring range
Resolution
Rated voltage
Short-circuit current
Accuracy

250V/200M

Ω

and 500V / 200M

Ω

0~19.99M

Ω

/ 199.9M

Ω

(2 auto ranges)

10k

Ω

/100k

Ω

250V/500V DC(+20%/-10%) @1M

Ω

14mA DC or less

±

(2% rdg+3dgt)

Range

Status

LED Color

Warning buzzer

(Continuous sounds)

RPE

1

Ω

RPE

1

Ω

RINS

1M

Ω

RINS

1M

Ω

Correct wiring

Faulty wiring

Green

Red

Green

Red

Green

Red

---

ON

---

ON

---

ON

Earth
Continuity

Insulation

Polarity(L/N/PE)

Advertising