Spectrex 20/20L (LB) - UV/IR Flame Detector User Manual

Page 22

Advertising
background image

Spectrex Inc. - SharpEye

TM

UV/IR Flame Detector Manual – TM20/20LB Rev E, August 2004

14

4.3.2 Alarm Delay Switch (SW2)
The detector is equipped with different Alarm Delay options. It provides
programmable time delays of 0 to 30 seconds with eight (8) fixed settings at: 0, 3,
5, 10, 15, 20, 25 and 30 seconds, using SW2 switches 1-3. See Table 5.
When an Alarm (Detection) level condition is encountered, the detector delays
execution of the Alarm Relay and the 4-20mA output by the specified period of
time. The detector will then evaluate the condition for required delay period. If the
Alarm level is still present, the Alarm indications return to its standby state.

Table 5. SW2 Alarm Delay Setting

Delay

SW2 switches

(seconds)

4

3

2

1

0 N/A

Off

Off

Off

3* N/A

Off

Off

On

5 N/A

Off

On

Off

10 N/A

Off

On

On

15 N/A

On

Off

Off

20 N/A

On

Off

On

25 N/A

On

On

Off

30 N/A

On

On

On

* Default

Note

: The new FM approval from January 2003 does not allow use of 20, 25 and

30-second delay settings.

Advertising