Spectrex 20/20L (LB) - UV/IR Flame Detector User Manual

Page 54

Advertising
background image

Spectrex Inc. - SharpEye

TM

UV/IR Flame Detector Manual – TM20/20LB Rev E, August 2004

46

2.1 Terminal Wiring
The detector contains a chamber consisting of a terminal block (Item 4). The
terminal block is labeled 1 to 6. (See Fig. No.10.)

Table 12. Terminals wiring options of the detector

Alarm Relay & 4-20mA Version

Option A (See Fig. No. 11)

Alarm & Fault Relays Version

Option B (See Fig. No. 12)

Power Supply
(Terminal Numbers 1, 2):Input power is
supplied to Terminal No. 1.RETURN is
connected to Terminal No. 2.

Power Supply

(Terminal Numbers 1, 2):Input power is
supplied to Terminal No. 1.RETURN is
connected to Terminal No. 2.

Alarm Relay

(Terminal Numbers 3, 4):

The Alarm output is a NO. SPST
contact at Terminal Numbers 3 and 4.
The contacts are closed at Alarm
Mode.

Alarm Relay

(Terminal Numbers 3, 4):

The Alarm output is a NO. SPST
contact at Terminal Numbers 3 and 4.
The contacts are closed at Alarm
Mode.

4-20mA Output

(Terminal Numbers 5,

6): Terminal Numbers 5 and 6 are used
for analog, 4-20mA current output as
specified in paragraph 4.e

Terminal No. 5 is used as output Terminal.
Terminal No. 6 is used as input Terminal.
see appendix B for more details)

Fault Relay

(Terminal Numbers 5, 6):

The Fault output is NC. SPST contact
at Terminal Numbers 5 and 6. The
contacts are open at Fault condition.

Figure 11: OPTION A

Flame Detector Assembly - Wiring

Diagram (“de version”)

Figure 12: OPTION B

Flame Detector Assembly - Wiring

Diagram (“de version”)