6 wiring (refer to fig. 5) – Spectrex 20/20L (LB) - UV/IR Flame Detector User Manual

Page 35

Advertising
background image

Spectrex Inc. - SharpEye

TM

UV/IR Flame Detector Manual – TM20/20LB Rev E, August 2004

27

6.6 Wiring (Refer to Fig. 5)


1 Disconnect

power.

2 Remove the four protective set-screws (Fig 4a, item 1) from detector front.

3

Release the four socket-head screws that secure the detector housing
(Item 3) to its back cover (Item 6) using No. 5 Hex Key for M6 screw. Hold
the housing during the removal of the screws. With the screws removed, pull
the detector housing from its cover. The cover remains attached to the
detector swivel mount. The housing slides under the cover and remains
attached to it by a securing cable (Item 8). The terminal board (Item 7) inside
the detector cover is now revealed.

4 Remove the protective plug mounted on the detector conduit inlet (Item 10).

Pull the wires through the detector cover (Item 6) and secure them firmly to
the cover using the cable-tie (Item 11) attached to it. Use a 3/4”-14NPT or
M25 x 1.5P explosion-proof conduit/cable gland connection.

5 Connect the wires to the required terminals (Item 7) according to the wiring

diagram. See section 6.7 and figures 6 and 7.

6 Connect a Grounding Cable to the Ground Terminal (Item 4) outside the

detector cover (Item 6). For FM installation connect the Grounding Cable to
the Ground Thread (Item 4) using appropriate screw.

The detector must be well grounded to Earth Ground for proper
operation.

7 Verify the wiring. Improper wiring may damage the detector.

8 Check the wires for secure mechanical connection and press them neatly

against the Terminal Board (Item 7) to prevent them from interfering while
closing the detector’s housing.