Spectrex 20/20R - Single IR Flame Detector User Manual

Page 15

Advertising
background image

Spectrex Inc. - SharpEye

TM

Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005

7

3.3 False Alarms Prevention
The detector will not provide an alarm or a warning signal as a reaction to the
radiation sources specified below.
Notes:
IAD = Immune at Any Distance.
All sources are chopped from 0 to 20Hz.

Table 3: Immunity To False Alarm Sources

Immunity

Distance

Radiation Source

ft

(m)

Incandescent frosted glass light, 100 W

1.7

0.5

Fluorescent light with white enamel reflector, standard office or
shop, 40 W (or two 20 W)

IAD

Arc welding [4 mm (5/32 in) rod; 240 A]

11.5

3.5

Halogen light 750W

16.5

5.5

Grinding metal

1.7

0.5

Lit cigar

3.3

1

Lit cigarette

1.7

0.5

Match, wood, stick including flare up

1.7

0.5