4.3.1 Function switch (SW1):
The user can select the desired mode of operation by means of this switch
according to table 5:

Table 5: Function Switch SW1

SW.

ON Position

OFF Position

1

Alarm latching - enabled

Alarm latching – disabled (default)

2

Accessory relay activated at warning
level

Accessory relay activated at
detection level (together with Alarm
relay) - (default)

3

Automatic & manual BIT (default)

Manual BIT only

4

Successful manual BIT activates the
Alarm relay and the 4-20mA output
turns to 15mA for approximately 3
seconds (default)

Successful manual BIT does not
activate the Alarm relay.

5

Successful manual BIT activates the
accessory relay and the 4-20mA
output turns to 10mA for
approximately 3 seconds (default)

Successful manual BIT does not
activate the Accessory relay.

6*

Sensitivity range – see table 6 below
(default)

Sensitivity range - see table 6

7*

Sensitivity range - see table 6 below Sensitivity range - see table 6

(default)

8

Accessory relay used as End Of
Line.

Accessory relay operates in
accordance with the settings of
SW1(default)

* See Table 6 for sensitivity range setting.

Table 6: Sensitivity range

Sensitivity

Range

SW1-7

SW1-6

1 (lowest)

16.5 ft (5m)

OFF

OFF

2 (highest)

50 ft (15m)

OFF

ON