Installation instructions – Spectrex 20/20R - Single IR Flame Detector User Manual

Page 30

Advertising
background image

Spectrex Inc. - SharpEye

TM

Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005

22

6. Installation Instructions

6.1 Scope
The "Spectrex" Model 20/20R is a self-contained Optical Flame Detector,
designed to operate as a stand-alone unit directly connected to alarm systems or
automatic fire extinguishing systems. The detector can form part of a more
complex system where many detectors and other devices are integrated through a
common control unit. This chapter does not attempt to cover all of the standard
practices and codes of installation. Rather, it emphasizes specific points of
consideration and provides some general rules for qualified personnel. Wherever
applicable, special safety precautions are stressed.

6.2 General Considerations

Very Important

The detector should be aimed toward the center of the detection zone and
have a completely unobstructed view of the protected area. Whenever
possible, the detector face should be tilted down at a slight angle to prevent
the accumulation of dust and dirt. Do not start an installation unless all
conceivable considerations regarding detector location have been taken into
account.

To ensure optimal performance and an efficient installation, the following
guidelines should be considered:

A. Sensitivity

To determine the level of sensitivity (SW1), the following issues should be
considered:

• Size of fire at determined distance to be detected.

• Type of flammable materials.

B. Spacing and Location

The number of detectors and their locations in the protected area are
affected by:

• Size of the protected area

• Sensitivity of the detectors

• Obstructed lines of sight

• Cone of view of the detectors

C. Environment

• Dust, snow or rain can reduce the detectors sensitivity and require

more maintenance activities.

• The presence of high intensity flickering of IR sources may affect

sensitivity.

Advertising