Spectrex 20/20R - Single IR Flame Detector User Manual

Page 17

Advertising
background image

Spectrex Inc. - SharpEye

TM

Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005

9

4.2 Output Signals

The detector controls the following outputs:

• Alarm relay

• Accessory relay

• Fault relay

• 4-20mA current output

• RS-485 communication


The detector can be in one of the following states.

Normal:

The detector is functioning normally.

BIT:

The detector performs a Built-In-Test.

Warning:

Fire detected - changed to warning – pre-alarm state.

Alarm:

Fire detected - changed to fire alarm state.

Latched Alarm
(Optional)

The alarm outputs are latched due to the detection of a fire that
has already been extinguished.

Fault:

A fault is detected during a BIT sequence or the power supply is
too low. In each state the detector will activate different outputs
as specified in table 5.

Table 4: Output Signals Versus Detector State

Detector
State

SW1

Power
Led

Alarm
Led

Alarm
Relay

Accessory
Relay

Fault
Relay

4-20mA
Output

Normal

On

Off

Off

Off

On

5mA

Warning

Sw1-2 ON On

Flash
2Hz

Off On

On 10mA

Alarm

On

On

On

On

On

15mA

Latch

Sw1-1 ON On

Off

On

Off

On

5mA

Fault

Flash

4Hz

Off Off Off

Off

0mA


• The detector will be in its FAULT state until it has passed a successful BIT.

• When SW1-2 is OFF, WARNING state is the same as the ALARM state.

• The alarm outputs will be activated as long as the alarm conditions are present

and will stop approximately 5 seconds after the fire is no longer detected.