Spectrex 20/20R - Single IR Flame Detector User Manual

Page 21

Advertising
background image

Spectrex Inc. - SharpEye

TM

Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005

13

4.3.3 Alarm Delay switch (SW3):
The detector is equipped with an Alarm Delay option, which provides
programmable time delays of 0 to 30 seconds with eight (8) fixed settings at: 0,
anti-flare, 3, 5, 10, 15, 20, and 30 seconds, using SW3 switches 1-3. See table 10.

When an Alarm (Detection) level condition is encountered, the detector delays the
execution of the Alarm output relay by the specified period of time. The detector
will then evaluate the condition for 3 seconds. If the Alarm level is still present, the
Alarm output will be activated. If this condition no longer exists, the detector will
return to its standby state. The Alarm delay option will affect the output relay and
the 4-20mA output but not the alarm LED.

Table 9: SW3 Alarm Delay Setting

SW3 switches

Delay (seconds)

4 3

2

1

0 ---

OFF

OFF

OFF

Anti Flare (default)

---

OFF

OFF

ON

3 ---

OFF

ON

OFF

5 ---

OFF

ON

ON

10 ---

ON

OFF

OFF

15 ---

ON

OFF

ON

20 ---

ON ON

OFF

30 ---

ON ON

ON


Note:

The new FM approval from January 2003 does not allow using 20 and 30

second delay.