Spectrex 20/20R - Single IR Flame Detector User Manual

Page 56

Advertising
background image

Spectrex Inc. - SharpEye

TM

Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005

48

2. W

IRING

(R

EFER TO

F

IG

. 18.)


1 Disconnect

power.

2 Release the four (4) slotted-head screws (item 3) that secure the chamber

cover (Item 2). The chamber is now revealed.

3

Remove the protective plug mounted on the detector electrical entry, pull the
wires through the detector chamber (Item 7). Use a 3/4"-14NPT or M25x1.5
explosion-proof conduit / cable gland connection to assemble the conduit /
cable to the detector.

4

Connect the wires to the required terminals (Item 4) according to the wiring
diagram. See paragraph 2.1 and figures no. 19 and no. 20.

5 Connect the grounding wire to the ground screw outside the detector cover

(Item 5).

The detector must be well grounded to Earth Ground for proper
operation.

6 Verify the wiring. Improper wiring may damage the detector.

7

Check the wires for secure mechanical connection and press them neatly
against the terminal to prevent them from interfering while closing the cover
(Item 2).

8

Place and secure the cover chamber (Item 2) using four (4) slotted-head
screws (Item 3).

Advertising