Spectrex Inc. - SafEye

TM

300 Gas Detector Manual – TM 794100, Rev. D, May 2004

11


Table 4. Standard (default) 4-20mA Current for the Gas Channel

Current

Status and Description

0mA +0.5mA

Fault 2 or Low Voltage

2mA ±0.5mA

Fault 1

4mA ±0.5mA

Zero reading - No gas detected

4-20mA

Continuous measuring of gas concentration at a range
between 0 and 5 LEL.m or full scale

21mA

Concentration is over the range limit (more than full scale
concentration).

Table 5. Discrete reading of 4-20mA at different detector’s modes

LEL.m Setting

Current Reading

Mode

301

302

0 +0.5mA

Fault 2 or Low Voltage

-

-

2 ±0.5mA

Fault 1

-

-

4 ±0.5mA

Standby

0

0

14 ±0.5mA

Warning

0.6

1

19 ±0.5mA

Alarm

1

2.5

3.7.2 Relays

The detector includes three relays:

Fault relay

Alarm relay

Accessory relay

Fault Relay contacts are normally energized closed, and opened when in Fault
condition

3.7.3 RS-485 Interface
The RS-485 input/output sends complete data information to a PC and receives
data or control commands from the PC. The communication with the PC is
operated through this interface is executed only when used with appropriate host
software.

The following PC minimal hardware requirements are as follows:

386 PC using DOS Ver. 5.0 or higher

1 MB RAM.

2 MB free hard disk space.

1.2 or 1.44 MB floppy drive

Color VGA

RS-485 Interface Card to be defined as COM1 or COM2. Isolated Adapter
is preferred.