Technical specifications – Spectrex Series 300 Open-Path Gas Detection System User Manual

Page 27

Advertising
background image

Spectrex Inc. - SafEye

TM

300 Gas Detector Manual – TM 794100, Rev. D, May 2004

19

4. Technical Specifications

4.1 General Specifications

Detected Gases: Simultaneous detection of C

1

-C

8

flammable gases

Detection Distance range:

Table 11: Detection Distance Range

Model No.

301

302

Distance (ft)

2-11.5

9.8-49

Distance (m)

0.6-3.5

3-15

Response Time

2 Sec.

10 Sec.



Spectral Response:

3.0 - 4.0 micron


Sensitivity Range:

Table 12: Sensitivity Range


Field of View:

Line of Sight

Alignment Tolerance:

± 2°

Drift:

Long term ± 5% of full scale

Temperature Range:

-40°F (-40°C) to +158°F (+70°C)

Immunity to false alarm:

Does not produce false alarm by Hydrocarbon
Flames and must of IR Radiation Sources.

301

302

Standard

0-2.5 LEL.m

0-5 LEL.m

DIPswitch

0-1 LEL.m

0-2 LEL.m

Advertising