Appendix A - Wire Selection Tables

General Instructions For Electrical Wiring

1. mA output or relay wiring - refer to Table 20 to determine the required wire

gauge for general wiring Calculate the permitted voltage fall with respect
to loads current, wire gauge and length of wires.

2. Power supply wires - refer to Table 21 to select wire gauge. DO NOT

connect any circuit or load to Detectors’ supply inputs.

Table 19. Maximum DC resistance at 68°F for copper wire

AWG # mm

2

Ohm per 100 ft.

Ohm/100

meter

26

0.12 - 0.15

4.32

14.15

24

0.16 - 0.24

3.42

11.22

22

0.30 - 0.38

1.71

5.60

20

0.51 - 0.61

1.07

3.50

18

0.81 - 0.96

0.67

2.20

16

1.22 - 1.43

0.43

1.40

14

1.94 - 2.28

0.27

0.88

12

3.09 - 3.40

0.17

0.55

10

4.56 - 6.64

0.11

0.35

1. Select "Number of Detectors" connected in one circuit.
2. Select "wiring length" per your installation requirements.
3. Refer to "power supply range" for voltage extreme applied.

Table 20. Wiring length in feet (meter)

No. of
Detectors

Recommended Wire Diameter

Power Supply
Range (VDC)

24

18

16

14

-

-

22-32

20

18

16

14

-

-

22-32

16

20

18

16

14

-

22-32

12

20

18

16

14

-

20-32

8

20

18

16

14

-

20-32

4 and less

20

18

16

16

14

20-32

Feet

164

328

492

656

820

(Meters)

(50)

(100)

(150)

(200)

(250)

Max. Length from Power Supply to Last

Detector