Spectrex Inc. - SafEye

TM

300 Gas Detector Manual – TM 794100, Rev. D, May 2004

17

Table 9 describes SW2 DIPswitches position and the required function for setting
the detector according to the necessary configuration

Table 9. SW2 DIPswitches Configuration

Switch

No.

Switch Definition

Off

position

On position

Default

setting

1

Address bit 0 (LSB)

0

1

off

2

Address bit 1

0

1

off

3

Address bit 2

0

1

off

4

Address bit 3

0

1

off

5

Address bit 4

0

1

off

6

Address bit 5 (MSB)

0

1

off

7

4-20mA direction
setting (1)

N/A

4-20mA output at source
position

on

8

4-20mA direction
setting (2)

N/A

4-20mA output at source
position

on

Alarm Options Selection Switch

This switch is used for the following function setting:

Selection of the Alarm status to be latched or to auto-reset after the Alarm
disappears.

Selection between two different 4-20mA reading modes, continuous
analog reading or discrete level reading which appropriate to the
detector’s status.


This switch also enables impedance matching to the serial link by providing a
connection to a loading resistor through the switch.