Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital
input di1/2/3 or the Ò-key.
Configuration, see page 27:

ConF / LOGI / Err.r

g

If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.

Self-tuning heating (

ADA.H) and cooling ( ADA.C) error status:

Operation

Operating KS4x-1

13

Maintenance manager / Error list

Name

Description

Cause

Possible remedial action

LooP

Control loop alarm

(LOOP)

- Input signal defective or not

connected correctly

- Output not connected

correctly

- Check heating or cooling circuit
- Check sensor and replace it, if necessary
- Check controller and switching device

AdA.H

Self-tuning heating

alarm
(ADAH)

- See Self-tuning heating error

status

- see Self-tuning heating error status

AdA.C

Self-tuning heating

alarm cooling
(ADAC)

- See Self-tuning cooling error

status

- see Self-tuning cooling error status

LiM.1

stored limit alarm 1

- adjusted limit value 1

exceeded

- check process

Lim.2

stored limit alarm 2

- adjusted limit value 2

exceeded

- check process

Lim.3

stored limit alarm 3

- adjusted limit value 3

exceeded

- check process

Inf.1

time limit value

message

- adjusted number of operating

hours reached

- application-specific

Inf.2

duty cycle message
(digital ouputs)

- adjusted number of duty

cycles reached

- application-specific

Error status

Description

Behaviour

0

No error

3

Faulty control action

Re-configure controller (inverse i direct)

4

No response of process

variable

The control loop is perhaps not closed: check sensor,

connections and process

5

Low reversal point

Increase (

ADA.H) max. output limiting Y.Hi or

decrease (

ADA.C) min. output limiting Y.Lo

6

Danger of exceeded set-point

(parameter determined)

If necessary, increase (inverse) or reduce (direct) set-point

7

Output step change too small

(dy > 5%)

Increase (

ADA.H) max. output limiting Y.Hi or reduce

(

ADA.C) min. output limiting Y.Lo

8

Set-point reserve too small

Increase set-point (invers), reduce set-point (direct)
or increase set-point range
(r

PArA / SEtp / SP.LO and SP.Hi )