Configuration level

Configuration

26

Operating KS4x-1

Name

Value range Description

Default

HC.SC

Solid state relay (SSR) short circuit signal (only visible

when O.TYP=0)

0

0

not active

1

active

timE

Timer end signal (only visible when O.TYP=0)

0

0

not active

1

active

P.End

Programmer end signal (only visible when O.TYP=0)

0

0

not active

1

active

FAi.1
FAi.2

INP1/ INP2 error (only visible when O.TYP=0)

1

0

not active

1

active

Out.0

-1999...9999

Scaling of the analog output for 0% (0/4mA or 0/2V, only

visible when O.TYP=1..5)

0

Out.1

-1999...9999

Scaling of the analog output for 100% (20mA or 10V, only

visible when O.TYP=1..5)

100

O.Src

Signal source of the analog output OUT3 (only visible when

O.TYP=1..5)

1

0

not used

1

controller output y1 (continuous)

2

controller output y2 (continuous)

3

process value

4

effective set-point Weff

5

control deviation xw (process value - set-point)

fOut

Forcing OUT3 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

g

Method of operation and usage of output

Out.1 to Out.3:

Is more than one signal chosen active as source, those signals are OR-linked.

LOGI

Name

Value range Description

Default

L_r

Local / Remote switching (Remote: adjusting of all values

by front keys is blocked)

0

0

no function (switch-over via interface is possible)

1

active

2

DI1

3

DI2 (only visible with OPTION)

4

DI3 (only visible with OPTION)

SP.2

Switching to second setpoint SP.2

0

0

no function (switch-over via interface is possible)

2

DI1

3

DI2 (only visible with OPTION)

4

DI3 (only visible with OPTION)