Technical data 52, Power supply 52, Technical data – West Control Solutions KS 42-1 User Manual

Page 52

Advertising
background image

Operating life
(electr.):

800.000 duty cycles with max.
rating

OUT3 USED AS RELAY OUTPUT

Contact type:

potential-free changeover contact

Max.contact rating:

500 VA, 250 V, 2A at 48...62Hz,
resistive load

Min. contact rating: 5V, 10 mA AC/DC
Operating life
(electr.):

600.000 duty cycles with max.
contact rating

Note:
If the relays OUT1...OUT3 operate external
contactors, these must be fitted with RC
snubber circuits to manufacturer specifications
to prevent excessive switch-off voltage peaks.

OUT3 AS UNIVERSAL OUTPUT

Galvanically isolated from the inputs.

Freely scalable
Resolution:

11 bits

Current output

0/4...20 mA configurable.
Signal range:

0...approx.22mA

Max. load:

£ 500 W

Load effect:

no effect

Resolution:

£22 mA (0,1%)

Accuracy

£ 40 mA (0,2%)

Voltage output

0/2...10V configurable
Signal range:

0...11 V

Min. load:

2 k

W

Load effect:

no effect

Resolution:

£ 11 mV (0,1%)

Accuracy

£20 mV (0,2%)

OUT3 used as transmitter supply

Output power:

22 mA /

³ 13 V

OUT3 used as logic output

Load

£ 500 W

0/

£ 20 mA

Load > 500

W

0/> 13 V

POWER SUPPLY

Dependent of order:

AC SUPPLY

Voltage:

90...250 V AC

Frequency:

48...62 Hz

Power consumption

approx. 7.3 VA

UNIVERSAL SUPPLY 24 V UC

AC voltage:

20,4...26,4 V AC

Frequency:

48...62 Hz

DC voltage:

18...31 V DC class 2

Power consumption:

approx.. 7.3 VA

BEHAVIOUR WITH POWER FAILURE

Configuration, parameters and adjusted
set-points, control mode:
Non-volatile storage in EEPROM

BLUEPORT FRONT INTERFACE

Connection of PC via PC adapter (see
"Accessory equipment"). The BlueControl
software is used to configure, set parameters
and operate the KS4x-1.

BUS INTERFACE (OPTION)

Galvanically isolated
Physical:

RS 422/485

Protocol:

Modbus RTU

Transmission speed: 2400, 4800, 9600, 19.200 bits/sec
Address range:

1...247

Number of controllers per bus:

32

Repeaters must be used to connect a higher number
of controllers.

ENVIRONMENTAL CONDITIONS

Protection modes

Front panel:

IP 65 (NEMA 4X)

Housing:

IP 20

Terminals:

IP 00

Permissible temperatures

For specified accuracy:

0...60°C

Warm-up time:

15 minutes

For operation:

-20...65°C

For storage:

-40...70°C

Humidity

75% yearly average, no condensation

Altitude

To 2000 m above sea level

Shock and vibration

Vibration test Fc (DIN 68-2-6)

Frequency:

10...150 Hz

Unit in operation:

1g or 0,075 mm

Unit not in operation: 2g or 0,15 mm

Technical data

52

Operating KS4x-1